UL 94 evaluates the burning behavior of small plastic specimens under controlled conditions. A material rating depends on specimen thickness and the report; it is not a guarantee of finished-cable or real-fire performance.

Horizontal burning HB

UL’s public explanation gives a burning-rate limit of ≤40 mm/min for specimens 3–13 mm thick and ≤75 mm/min below 3 mm. Consult the applicable complete standard for testing and classification.

Vertical burning V-0, V-1 and V-2

The flame is applied twice for 10 seconds each. This table summarizes key criteria and does not replace the complete procedure and standard.

CriterionV-0V-1V-2
Afterflame time after each flame application (s)≤10≤30≤30
Total afterflame time, 5 specimens and 10 flame applications (s)≤50≤250≤250
Afterflame plus afterglow after the second application (s)≤30≤60≤60
Burning drips ignite cottonNot permittedNot permittedPermitted
Burning reaches the clampNot permittedNot permittedNot permitted